You can use the Ewon to access remotely a Mitsubishi® PLC.

Prior to the in-depth PLC configuration, the right-sided picture shows the network parameter configuration of the GX Works Mitsubishi software.

Different simplified configurations are explained depending on the model of the PLC.

  • Q series with QJ71E71 extension card
  • QCPU series
  • FX series with FX3U-ENET extension card
  • FX3GE series
  • FX5U series
You can find a more detailed version of how to remote access a Mitsubishi® PLC in the Documentation section here under or in the Downloads and Documentation.
Mitsubishi - GX Works - Network Parameter

PLC tagged as Q series

With the QJ71E71 extension card

The QJ71E71 extension card provides an additional Ethernet port which is used to configure the GX Works software, provided by Mitsubishi.

The summary of the configuration process is shown in the picture.


Mitsubishi - Melsoft - qj71e71 - Summary

Step #1

In the Transfer Setup window, select Ethernet board in the PC side I/F row of the Transfer Setup frame.

It may happen that on some interfaces of old software versions, you are asked to define a station number. This would be the definition of the station number which corresponds to the station number of the PC. This one must be different from the PLC’s station number.

Hit the OK button.


Mitsubishi - Melsoft - qj71e71 - Step 1

Step #2

Click Ethernet module in the PLC side I/F row.

Give the IP address and the station number of the PLC. Remember to differentiate the station number (between the PC and the PLC).

Hit the OK button.


Mitsubishi - Melsoft - qj71e71 - Step 2

Step #3

Click on Other station (single network) in the Other station row.

Set the communication time checker. Hit the OK button.


Mitsubishi - Melsoft - qj71e71 - Step 3

Step #4

Select Ethernet in the Network route section.

Check the option Access to Ethernet module set on PLC side I/F.

Hit the OK button.


Mitsubishi - Melsoft - qj71e71 - Step 4

Step #5

You are done with the configuration of the software.

Perform a test connection to make sure everything is working as it should.


With the QCPU series

The QCPU provides an embedded Ethernet port which is used to configure the GX Works software, provided by Mitsubishi.

The summary of the configuration process is shown in the picture.


Mitsubishi - Melsoft - QCPU - Summary

Step #1

In the Transfer Setup window, select Ethernet board in the PC side I/F row.

Once the new window is displayed, set the protocol field to TCP.

It may happen that on some interfaces of old software versions, you are asked to define a station number. This would be the definition of the station number which corresponds to the station number of the PC. This one must be different from the PLC’s station number.

Hit OK to come back to the main window.


Mitsubishi - Melsoft - QCPU - Step 1

Step #2

Click PLC module in the PLC side I/F row. Two things to do:

  • Set the PLC mode to QCPU (Qmode), if not already.
  • Provide the IP address of the PLC.

Hit OK to come back to the main window.


Mitsubishi - Melsoft - QCPU - Step 2

Step #3

Click No specification in the Other station row.

As a new window appears, set the relevant communication time checker.

Hit OK to come back to the main window.


Mitsubishi - Melsoft - qj71e71 - Step 3

Step #4

The software is now configured to remotely access your PLC.

Perform a test connection to make sure everything is working as it should.


PLC tagged as FX series


With a FX3U-ENET extension card

The FX3U-ENET extension card provides an additional Ethernet port which is used to configure the GX Works software, provided by Mitsubishi.


  1. In the Transfer Setup window, select Ethernet board in the PC side I/F row.
    It may happen that on some interfaces of old software versions, you are asked to define a station number. This would be the the station number of the PC that has to be different from the PLC station number.
  2. Select Ethernet module in the PLC side I/F row.
  3. Select your FX3U-ENET extension card.
  4. Put the IP address of the PLC.
  5. You are done configuring the software.
    Perform a test connection to make sure everything is working as it should.

Mitsubishi - GX Works - FX3U - Configuration

With the FX3GE series

The FX3GE series provides an embedded Ethernet port which is used to configure the GX Works software, provided by Mitsubishi.

The summary of the configuration process is shown in the picture.


Mitsubishi - Melsoft - QCPU - Summary

Step #1

In the Transfer Setup window, select Ethernet board in the PC side I/F row.

It may happen that on some interfaces of old software versions, you are asked to define a station number. This would be the definition of the station number which corresponds to the station number of the PC. This one must be different from the PLC’s station number.

Hit OK to come back to the main window.


Mitsubishi - Melsoft - QCPU - Step 1

Step #2

Select PLC module in the PLC side I/F row.

Check the Connection via HUB box and provide the IP address of your PLC.


Mitsubishi - GX Works - FX3GE - Step 2

Step #3

Click No Specification from the Other Station Setting row.

You're done with the configuration of the software.
Perform a test connection to make sure everything is working as it should.


PLC tagged as iQ-F series


With the FX5U series

The FX5U provides an embedded Ethernet port which is used to configure the GX Works software, provided by Mitsubishi.

The summary of the configuration process is shown in the picture.



Mitsubishi - Melsoft - QCPU - Summary

Step #1

In the Transfer Setup window, select Ethernet board in the PC side I/F row.

It may happen that on some interfaces of old software versions, you are asked to define a station number. This would be the definition of the station number which corresponds to the station number of the PC. This one must be different from the PLC’s station number.

Hit OK to come back to the main window.


Mitsubishi - Melsoft - QCPU - Step 1

Step #2

Select PLC Module in the PLC side I/F row.

Check the Connection via HUB and provide the IP address of the PLC.


Mitsubishi - GX Work - FX5U - Step 2

Step #3

Configuration is done.

Perform a test connection to make sure everything is working as it should.


Documentation

技术支持

Product name
订货号:

分步指南

  • 准备
  • 安装
  • 配置

资源

  • 下载和文档
  • FAQ
  • 故障排除

服务和培训

  • 技术服务
  • HMS学院培训
Request support

联系支持

解决方案

工厂主
机器制造商

产品

Cosy
Flexy
Netbiter – Argos
Talk2M

 

Support

Cosy
Flexy
Netbiter – Argos
Firmware & Software
All Documents
Talk2M Status
Tips & News

公司

安全
我们的故事
市场活动
News
招贤纳士
合作伙伴

博客

案例研究

 

联系方式

喜欢我们 关注我们 观看我们视频 加入我们 新闻订阅
我们的品牌:Anybus Ixxat Ewon Intesis
HMS
版权©2020 瑞典HMS工业网络有限公司北京代表处—版权所有。
Menu
  • Cookies
  • 隐私政策
  • 使用条款
  • 保修

We use cookies on this site to enhance your user experience

By clicking any link on this page you are giving your consent for us to set cookies.

I want to find out more Yes, I agree